Type:thermocouple (thermal resistance) for power station

Illustrate:It is specially designed for power station to measure temperature for 30KW, 60KW power-generating set and concerned equipments. It is used to directly measure the temperature of liquid, vapor, gas, and solid surface ranging from-200℃ to 800℃ during production process.

Thermocouple (Thermal Resistance) for Power Station
 

Application
It is specially designed for power station to measure temperature for 30KW, 60KW power-generating set and concerned equipments. It is used to directly measure the temperature  of liquid, vapor, gas, and solid surface ranging from-200℃ to 800℃ during production process.
Operation Theory
Thermocouple electrodes are made of two different materials. Temperature difference between measuring end and reference end results in pyroelectric potential, then display meter indicates the corresponding temperature to the pyroelectic potential.
It is based on that temperature change of material results in change of its resistance. When resistance value changes, the working instrument will display relevant temperature value.
 
Main Technical Parameters
Executive Standard
IEC584
GB/T16839-1997
JB/T8622-1997
JB/T8623-1997
 
Measuring Range & Tolerance
Thermocouple
 

Type Graduation Tolerance Class
I II
Tolerance Value Measuring Range °C Tolerance Value Measuring Range °C
WRN K ±1.5°C -40~+375 ±2.5 °C -40~+333
±0.004ltl 375~1000 ±0.0075 ltl 333~1200
WRE E ±1.5°C -40~+375 ±2.5°C -40~+333
±0.004 ltl 375~1000 ±0.0075 ltl 333~900
 
Thermal Resistance
 

Type  Graduation Measuring Range ℃ Accuracy  Tolerance
WZP Pt100 -200~+500 A
B
±(0.15+0.002) ltl
±(0.30+0.005) ltl
WZC Cu50  
Cu100
-50~+100 --- ±(0.30+0.005) ltl
 Note: It is absolute temperature value actually tested with thermal sensor.
 
Insulation Resistance at Normal Temperature
 
The insulation resistance between electrode and protection tube of thermocouple shall be no less than 1000Ω.m under condition that environment temperature is 20±15℃,relative humidity is no more than 80%, and testing voltage is D.C.500±50V.
 
The insulation resistance between electrode and protection tube of thermal resistance shall be no less than 100M Ωunder condition that environment temperature is 15~35℃,relative humidity is no more than 80%, and testing voltage is D.C.10~100V.